(b) Final effluent storage facilities shall meet all setback requirements for riparian buffer rules pursuant to 15A NCAC 02B, as well as the following setbacks:
feet
Each private or public water supply source 100
Surface waters such as intermittent and perennial streams, perennial waterbodies,
and wetlands 50
Each well with exception of monitoring wells 100
Each property line for facilities constructed on or after June 18, 2011 50
Each property line for facilities constructed prior to June 18, 2011 0
(c) The setbacks for utilization sites where reclaimed water is land applied shall be as follows:
feet
Surface waters such as intermittent and perennial steams, perennial waterbodies,
and wetlands not classified SA 25
Surface waters such as intermittent and perennial streams, perennial waterbodies,
and wetlands not classified SA, provided that the reclaimed water to be
utilized contains no more than 10 mg/L of Total Nitrogen and no more
than 2 mg/L of Total Phosphorusin addition to applicable requirements
in Rule .0101 of this Subchapter and Section .0300 of this Subchapter 0
Surface waters such as intermittent and perennial streams, perennial waterbodies,
and wetlands classified SA 100
Each well with exception of monitoring wells 100
History Note: Authority G.S. 143-215.1; 143-215.3(a);
Eff. June 18, 2011;
Readopted Eff. March 21, 2019.