15A NCAC 02T .0305
(a) Sewer and sewer extensions shall not be constructed in the following areas:
(b) Engineering design documents. The following documents shall be prepared prior to submitting a permit application to the Division. If submittal of such documents is not requested in the permitting process (i.e., fast-track), they shall be available upon request by the Division. If required by G.S. 89C, a professional engineer shall prepare these documents:
[Note: The North Carolina Board of Examiners for Engineers and Surveyors has determined, via letter dated December 1, 2005, that preparation of engineering design documents pursuant to this Paragraph constitutes practicing engineering under G.S. 89C.]
(f) The following separations shall be provided from the sewer system to the listed feature except as allowed by Paragraph (g) of this Rule:
Storm sewers and other utilities not listed below (vertical) 18 inches
Water mains (vertical-water over sewer including in benched trenches) 18 inches
or (horizontal) 10 feet
Reclaimed water lines (vertical – reclaimed over sewer) 18 inches
or (horizontal) 2 feet
Any private or public water supply source consisting of wells, WS-I waters, Class I, Class II, or Class III
reservoirs used as a source of drinking water 100 feet
Waters classified WS-II, WS-III, WS-IV, B, SA, ORW, HQW, or SB from normal high water or tide elevation, wetlands that are directly abutting these waters, and wetlands classified as UWL or SWL 50 feet
Any other stream, lake, impoundment, wetlands classified as WL, waters classified as C, SC, or WS-V, or
ground water lowering and surface drainage ditches 10 feet
Any building foundation 5 feet
Any basement 10 feet
Top slope of embankment or cuts of 2 feet or more vertical height 10 feet
Drainage systems and interceptor drains 5 feet
Any swimming pool 10 feet
Final earth grade (vertical) 36 inches
(g) The following separations shall be permitted if separations in Paragraph (f) of this Rule cannot be achieved, provided that nothing in this Paragraph shall supersede the allowable alternatives provided in the Commission for Public Health Public Water Supply Rules (15A NCAC 18C), Commission for Public Health Sanitation Rules (15A NCAC 18A) or the Groundwater Protection Rules (15A NCAC 02L and 15A NCAC 02C) that pertain to the separation of sewer systems from water mains or public or private wells:
(h) The following criteria shall be met for all pumping stations and force mains:
(1) Pump Station Reliability:
(i) The following criteria shall be met for gravity sewers:
(j) The following criteria shall be met for low pressure sewers, vacuum sewers, STEP, and other alternative sewers discharging into another sewer system:
History Note: Authority G.S. 143-215.1; 143-215.3(a);
Eff. September 1, 2006;
Readopted Eff. September 1, 2018;
Amended Eff. April 1, 2021.