13 NCAC 13 .0412
(d) For a closed type system the expansion tank shall be not less than that determined as follows:
Vt = [(0.00041T - 0.0466)Vs]/[(Pa/Pf) - (Pa/Po)] where:
Vt = minimum volume of tank(s), gal
Vs = volume of system, not including tanks, gal
T = average operating temperature, deg F
Pa = atmospheric pressure, psi
Pf = fill pressure, psi
Po = maximum operating pressure, psi.