04 NCAC 11 R07-29
(b) Meter Test Flows. - The following test rates are recommended for conducting test:
It is recommended that no less than three rates of flow be used.
Allowable Range Test Flow Recommended Test
Meter Gallons per Minute Rate Flow Gallons per Minute
Size Min. Max. Min. Med. Max.
1 ½ 5 100 5 25 100
2 8 160 8 40 160
3 16 300 15* 100 300
4 28 500 15* 250 500
6 48 1000 20* 500 1000
*Note - A meter failing to register 5% of the water passed at those rates marked * should not be installed without correction.