Md. Code Regs. 26.10.17.11
Normal and Emergency Venting.
Effective Jun 13, 202249:12 Md. R. 642Environment Article, §§4-401—4-403, 4-405, 4-406, 4-408, 4-410—4-412, 4-415-1—4-418, 4-501, and 4-502, Annotated Code of Maryland
A. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST shall ensure the normal venting for the shop-fabricated AST meets the following requirements:
(1) Design and construct the normal venting in accordance with one of the following industry standards:
- (a) UL 142 “Standard for Safety, Steel Aboveground Tanks for Flammable and Combustible Liquids”; or
- (b) API Standard 2000 “Venting Atmospheric and Low-pressure Storage Tanks”;
- (2) The normal venting requirements for ASTs listed in NFPA 30 “Flammable and Combustible Liquids Code”; and
- (3) Vent an atmospheric pressure AST to prevent the development of vacuum or pressure above a 1.0 psi (6.9 kPa) maximum operating pressure.
B. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST shall ensure the emergency venting for the shop-fabricated AST meets the following requirements:
(1) Design and construct emergency venting in accordance with one of the following industry standards:
- (a) UL 142 “Standard for Safety, Steel Aboveground Tanks for Flammable and Combustible Liquids”; or
- (b) API Standard 2000 “Venting Atmospheric and Low-pressure Storage Tanks”; and
- (2) Emergency venting meets the requirements in NFPA 30 “Flammable and Combustible Liquids Code”.
Authority: Environment Article, §§4-401—4-403, 4-405, 4-406, 4-408, 4-410—4-412, 4-415-1—4-418, 4-501, and 4-502, Annotated Code of Maryland
Effective date: June 13, 2022 (49:12 Md. R. 642)