Md. Code Regs. 20.70.06.03
A. Procedure. The following procedures shall apply to the testing and adjusting of meters and associated devices:
B. Test Flows. For determination of minimum test flow and other normal test flows, the Commission will use as a guide the appropriate standard specifications of the American Water Works Association for the various types of meters. These flows for displacement type cold water meters are as follows:
| Meter Size Inches | Minimum Test Flow Gallons per Minute | Maximum Normal Flow Gallons per Minute |
|---|---|---|
| 5/8 | 1/4 | 20 |
| 3/4 | 1/2 | 30 |
| 1 | 3/4 | 50 |
| 1-1/2 | 1-1/2 | 100 |
| 2 | 2 | 160 |
| 3 | 4 | 300 |
| 4 | 7 | 500 |
| 6 | 12 | 1000 |
C. Tests to Determine Error in Registration. Meters shall be tested at the following three flows:
Authority: Public Utilities Article, §§2-121, 5-101, and 5-303, Annotated Code of Maryland
Effective date: July 1, 1968 (Order No. 57171)