- A. Approved. Utilities may test meters by other methods approved by the Commission or by use of other working standards approved by the Commission.
- B. Accuracy. The approved working standards shall be maintained in good condition and correct adjustment, shall have a high degree of repeatability, and shall be capable of determining the actual proof of the meter under test to within ±0.5 percent at rates of flow between 15 percent and 100 percent of rated capacity of the meter under test.
- C. Test Period. The approved working standards shall be tested for accuracy by comparison with an acceptable standard at least once each 3 years.
Authority: Public Utilities Article, §§2-121, 5-101, and 7-301, Annotated Code of Maryland
Effective date: July 1, 1964 (Order No. 55567)
Chapter revised effective October 21, 1974 (Order No. 60922)
Regulation .01C amended effective February 7, 2000 (27:2 Md. R. 146)
Regulation .02 amended effective May 5, 1986 (13:9 Md. R. 1032); February 7, 2000 (27:2 Md. R. 146)
Regulation .03A amended effective February 7, 2000 (27:2 Md. R. 146)
Regulation .04 amended effective February 7, 2000 (27:2 Md. R. 146)