Md. Code Regs. 20.50.07.02
A. Secondary Voltages. The voltage at the utility's service terminals, as installed for each customer, shall be maintained within the Limits specified in the table below. If a utility adopts any standard voltage not included in the table, it shall advise the Commission in order that the Commission may establish appropriate voltage limits. When 3-phase service is provided, the utility shall exercise reasonable care to assure that the phase voltages are balanced.
| Standard | Minimum | Maximum |
|---|---|---|
| 120 | 114 | 126 |
| 120/208 | 114/197 | 126/219 |
| 120/240 | 114/228 | 126/252 |
| 208 | 197 | 219 |
| 240 | 216 | 252 |
| 240/416 | 228/395 | 252/437 |
| 240/480 | 228/456 | 252/504 |
| 265/460 | 238/414 | 278/483 |
| 277/480 | 249/432 | 291/504 |
| 440 | 396 | 462 |
| 460 | 414 | 483 |
| 480 | 432 | 504 |
| 600 | 540 | 630 |
B. Primary Voltages. The following limits shall apply where the utility supplies service at primary voltage:
C. Exceptions to Voltage Requirements. It will not be considered a violation when voltages outside of the prescribed limits are caused by any of the following:
Authority: Public Utilities Article, §§2-121, 5-101, and 5-303, Annotated Code of Maryland
Effective date: May 22, 1942 (Order No. 38330)
Chapter revised effective May 18, 1960 (Order No. 54348)
Chapter revised effective June 1, 1965 (Order No. 55819)
Regulation .03C amended effective June 6, 2005 (32:11 Md. R. 983)
Regulation .05 amended effective April 15, 2002 (29:7 Md. R. 622)
Regulation .05B amended effective May 28, 2012 (39:10 Md. R. 661)
Regulation .06 adopted effective April 15, 2002 (29:7 Md. R. 622)
Regulation .06 repealed effective May 28, 2012 (39:10 Md. R. 661)
Regulation .07 adopted effective April 15, 2002 (29:7 Md. R. 622)
Regulation .07 repealed effective May 28, 2012 (39:10 Md. R. 661)