310 C.M.R. 80.63
(1) If at any time after a standby trust is funded upon the instruction of the Department with funds drawn from a guarantee, local government guarantee with standby trust, letter of credit, or surety bond, and the amount in the standby trust is reduced below the full amount of coverage required, the Owner or Operator shall by the anniversary date of the financial mechanism from which the funds were drawn:
80.64 Requirements for Airport Hydrant Fuel Distribution Systems
(1) Owners and Operators of airport hydrant systems shall comply with the requirements of 310 CMR 80.00 as follows:
(a) For airport hydrant systems installed on or before October 1, 2021 the requirements are effective according to the following schedule:
Requirements Effective Dates
Spill bucket requirements, if applicable at 310 CMR 80.21 and No later than October 13, 2022 80.28; overfill prevention equipment requirements at 310 CMR 80.21 and 80.28; corrosion protection requirements at 310 CMR 80.22, 80.29 and 80.64(7); compatibility requirements at 310 CMR 80.30; walkthrough requirements at 310 CMR 80.35 and 80.64(8); and operator training at 310 CMR 80.37 Recordkeeping requirements at 310 CMR 80.36 associated with No later than October 13, 2022 regulatory requirements effective October 13, 2022 Leak detection at 310 CMR 80.19, 80.26 and 80.64(9) No later than October 13, 2022 Registration and reporting requirements at 310 CMR 80.23 October 1, 2021 (except as provided in 310 CMR 80.64(2); repair requirements at 310 CMR 80.33; Compliance Certification requirements at 310 CMR 80.34; release reporting, response, and investigation at 310 CMR 80.38 through 80.40; closure requirements at 310 CMR 80.41 through 80.47; financial responsibility at 310 CMR 80.51 through 80.63 except as provided in 310 CMR 80.64(3))
Recordkeeping requirements at 310 CMR 80.36 associated with October 1, 2021 the requirements effective October 1, 2021
(7) Corrosion Protection.
(8) Periodic Inspections. In addition to the periodic inspection requirements in 310 CMR 80.35, Owners and Operators shall inspect the following additional areas of airport hydrant systems at least once every 30 days if confined space entry according to the Occupational Safety and Health Administration (see 29 CFR part 1910) is not required or at least annually if confined space entry is required and keep documentation of the inspection according to 310 CMR 80.35(4).
(9) Leak Detection for Piping.
(a) Methods of leak detection for underground piping associated with airport hydrant systems shall follow either the requirements in 310 CMR 80.19 and 80.26 or use one or a combination of the following alternative methods of leak detection:
1. Perform a semiannual or annual line tightness test at or above the piping operating pressure in accordance with the table below.
Maximum Leak Detection Rate per Test Section Volume
Test Section Volume Semiannual Test - Annual Test - (Gallons) Leak Detection Rate Not To Leak Detection Rate Not To
Exceed (Gallons Per Hour) Exceed (Gallons Per Hour)
< 50,000 1.0 0.5 ≥ 50,000 to < 75,000 1.5 0.75 ≥ 75,000 to < 100,000 2.0 1.0 ≥ 100,000 3.0 1.5
Piping segment volumes ≥ 100,000 gallons not capable of meeting the maximum 3.0 gallon per hour leak rate for the semiannual test may be tested at a leak rate of up to 6.0 gallons per hour according to the following schedule:
Phase In For Piping Segments > 100,000 Gallons In Volume
First test No later than October 13, 2022, may use
up to 6.0 gph leak rate
Second test Between October 14, 2022 and
October 13, 2027, may use up to 6.0 gph leak rate
Third test Between October 14, 2027 and
October 13, 2028, shall use 3.0 gph for leak rate
Subsequent tests After October 14, 2028, begin using
semiannual or annual line testing according to the Maximum Leak Detection Rate Per Test Section Volume Table C above
(b) If a release or leakage is indicated by alarm other otherwise, the Owner or Operator shall immediately commence an investigation to determine whether there is a release or leakage.
(10) Spill Buckets.
REGULATORY AUTHORITY
310 CMR 80.00: M.G.L. c. 21O, § 5, c. 21C, c. 21E, § 6 and c. 21A, § 16.