248 C.M.R. 5.09
9.1.1* Appliances, Equipment, and Accessories to be Approved. Board Required Product Acceptance. Only products and materials that meet the product acceptance requirements of 248 CMR 3.04(1): Board Required Product-acceptance may be utilized in gas fitting work in Massachusetts unless the Board has waived the necessity for product acceptance per 248 CMR 3.04(1)(h).
9.1.1.3 Unlisted Appliances, Equipment, and Accessories. Acceptance of unlisted gas appliances, equipment, and accessories shall require a variance by the Board.
9.1.19.1 Vent Lines.
(a) Vent lines shall be steel, wrought iron pipe, or corrugated stainless steel tubing (CSST). Vents shall be:
(c) Vent lines that terminate outside a building or structure shall be located no less than:
(d) Vent lines that penetrate roofs and sidewalls shall be run through metallic sleeves that are sealed from the weather and insects, and:
(f) Appliance pressure regulators shall not be connected to a common manifold.
TABLE 9.1.19.1
Minimum Schedule 40 Pipe Size/CSST for
Venting of Gas Components Maximum lengths of iron pipe or corrugated stainless steel tubing
Gas Components (CSST) from components to outside the building
0 - 40 feet 0 - 100 feet 0 - 200 Feet
Main Gas Pressure Regulator - Steel Pipe Size ¾ inch IPS 1 inch IPS 1¼ inch IPS - CSST Size (Low Pressure 30/31 EHD 37 EHD 46/48 EHD Gas only)
High & Low Gas Pressure Switches When Manifolded - Steel Pipe Size ¾ inch IPS 1 inch IPS 1½ inch IPS - CSST Size (Low Pressure 30/31 EHD 37 EHD 60/62 EHD Gas only)
TABLE 9.1.19.1 (continued)
Minimum Schedule 40 Pipe Size/CSST for
Venting of Gas Components
Gas Components Maximum lengths of iron pipe or corrugated stainless steel tubing
(CSST) from components to outside the building
0 - 40 feet 0 - 100 feet 0 - 200 Feet
Block and Bleed Valves (when used) - Steel Pipe Size Full IPS Relief Increase Increase IPS/CSST - CSST Size (Low Pressure IPS/CSST one two Sizes Gas only) Size
9.1.22 Installation Instructions.
9.1.23 Carbon Monoxide Protection. No installation or replacement of a vented gas appliance shall be permitted unless a battery powered or electrically hard wired carbon monoxide detector is present on the same floor as the appliance or on the next adjacent floor when the appliance is located in a crawl space unless the appliance is located in a detached, uninhabitable garage. For all residential dwellings, a carbon monoxide detector must also be present on each habitable level of the dwelling. These requirements shall not be deemed to waive any additional requirements imposed by M.G.L. c. 148 § 26F½.
Sufficient clearance must also be provided to allow the total replacement of the appliance or equipment.
9.6.1.4 General Requirements for Connectors.
9.6.3.5 Flexible gas hoses used to connect portable and mobile industrial appliances shall not exceed a length of 20 feet.
Such piping shall also be installed in a manner not to interfere with the total replacement of the appliance or equipment.