A. Upon installation of any new fire sprinkler system, the system shall have a placard permanently affixed on each riser. The installation placard shall be a minimum of
2 3/4 inches by 2 3/4 inches. Maximum size cannot exceed
5 inches by 5 inches. The following information and wording shall be required to be preprinted on the front side of the tag:
- 1. DO NOT REMOVE BY ORDER OF THE STATE FIRE MARSHAL (all capital letters, in bold type);
- 2. installation placard;
- 3. installation date;
- 4. firm's name;
- 5. firm's certificate number;
- 6. qualifier's name;
- 7. qualifier's license number;
- 8. NFPA Code Edition System was installed under;
- 9. plan review or exemption number;
- 10. model number and manufacturer of sprinkler valve;
- 11. model number and date of each type of sprinkler head on system.
- B. If after initial installation a sprinkler system is redesigned because of an occupancy change or the main control valve is replaced for any reason, a new installation placard shall be completed and attached as above, noting the appropriate changes in information.
Authority Note
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:1664.2 et seq.
Historical Note
HISTORICAL NOTE: Promulgated by the Department of Public Safety and Corrections, Office of State Fire Marshal, LR 35:682 (April 2009).