LAC 51:XIV.505
A. Water heaters installed in residential occupancies may be sized in accordance with the following Table 505.
| Table 505 Minimum Capacities For Water Heaters1,2 | |||
| Number of Bathrooms | 1 to 1.5 | 2 to 2.5 | 3 to 3.5 |
| Number of Bedrooms | 1 2 3 | 2 3 4 5 | 3 4 5 6 |
| First Hr Rating Gal. | 42 54 54 | 54 67 67 80 | 67 80 80 80 |
| Nom. Tank Size, Gal. Gas Water Heaters | 20 30 30 | 30 40 40 50 | 40 50 50 50 |
| Elect. Water Heaters | 30 50 50 | 50 66 66 80 | 66 80 80 80 |
| Oil Water Heaters | 30 30 30 | 30 30 30 30 | 30 30 30 30 |
NOTES:
1. The main criteria for a properly sized water heater is a sufficient first hour rating to meet peak hot water demand. The majority of tank sizes shown in the table will have a first hour rating equal to or greater than the first hour rating indicated. A water heater with a smaller tank size than shown in the table but with a sufficient first hour rating shall be permitted.
2. The first hour rating is found on the "Energy Guide" label.
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4(A)(7) and R.S. 40:5(2)(3)(7)(9)(16)(17)(20).
HISTORICAL NOTE: Promulgated by the Department of Health and Hospitals, Office of Public Health, LR 38:2828 (November 2012).