A. The following conditions are considered treatment technique triggers.
- 1. For systems collecting 40 or more distribution system samples per month, more than 5.0 percent of the monthly samples are total coliform positive.
- 2. For systems collecting less than 40 distribution system samples per month, two or more samples per month are total coliform positive.
- 3. Failure to collect every required repeat sample following a total coliform positive sample.
4. An E.coli maximum contaminant level (MCL) violation occurs as specified below:
- a. a coliform-positive original sample that is also positive for E. coli is followed by a coliform-positive repeat sample;
- b. a coliform-positive original sample followed by a coliform-positive repeat sample is also positive for E. coli;
- c. failure to take all repeat samples following an E. coli positive routine sample; or
- d. failure to test for E. coli on any repeat total coliform positive sample.
- 5. A second occurrence of conditions under Paragraph 1, 2 or 3 of this Subsection within a rolling 12-month period.