A. Booster pumps shall be located or controlled so that:
- 1. they will not produce negative pressure in their suction lines;
- 2. pumps taking suction from storage tanks shall be provided adequate net positive suction head;
- 3. pumps taking suction from ground storage tanks shall be equipped with automatic shutoffs or low pressure controllers as recommended by the pump manufacturer;
- 4. automatic or remote control devices shall have a range between the start and cutoff pressure which will prevent excessive cycling; and
- 5. a bypass is available.
B. Inline Booster Pumps. In addition to the other requirements of this section, inline booster pumps shall:
- 1. be accessible for servicing and repairs;
- 2. maintain inlet pressure installed in the distribution system as required in §237.A of this Part under all operating conditions;
- 3. maintain at least 20 psig (140 kPa) in the suction line under all operating conditions with automatic shutoff or low pressure controller, unless otherwise acceptable to the state health officer; and
- 4. have a bypass.
Authority Note
AUTHORITY NOTE: Promulgated in accordance with the provisions of R.S. 40:4(A)(8), 40:4.13.D.(1)(2) and 40:5(A)(2)(3)(5)(6)(7)(17).
Historical Note
HISTORICAL NOTE: Promulgated by the Department of Health, Office of Public Health, LR 44:334 (February 2018), effective August 1, 2018.