A. Both raw and finished water pumping stations shall:
- 1. be of durable construction, fire and weather resistant;
- 2. have any underground structure waterproofed
- 3. have all floors slope to a suitable drain in such a manner that the quality of the potable water will not be endangered;
- 4. provide a suitable outlet for drainage without allowing discharge across the floor, including pumping glands, vacuum air relief valves, etc.
B. A suction well is a component(s) designed to facilitate the suction of water by way of pump excluding intake structures, ground storage tanks and clearwells. Suction wells shall:
- 1. be watertight;
- 2. have floors sloped to permit removal of water and settled solids;
- 3. be covered or otherwise protected against contamination; and
- 4. have two pumping compartments or other means to allow the suction well to be taken out of service for inspection maintenance or repair.
C. Equipment servicing pump stations shall:
- 1. provide adequate facilities or other means for servicing or removal of pumps, motors or other heavy equipment; and
- 2. have openings in floors, roofs or wherever else needed for removal of heavy or bulky equipment.
D. Stairways or ladders shall:
- 1. be provided between all floors, and in dry pits or compartments which must be entered; and
- 2. conform to the applicable requirements of the state and local building codes.