Kan. Admin. Regs. § 4-27-19
(a) Each licensee shall ensure that the electrical wiring is installed and maintained in accordance with all applicable local electrical codes. In the absence of local electrical codes, the electrical wiring shall be installed and maintained by a licensed electrician. Each licensee shall ensure that all of the following requirements are met:
(1)(A) Each newly constructed lodging establishment shall have a ground-fault circuit interrupter in each electrical outlet located within five feet of any water source, including a swimming pool and hot tub.
(C) Each licensee shall ensure that the lodging establishment has a ground-fault circuit interrupter in each electrical outlet located within five feet of any water source, including a swimming pool and hot tub.
(3) All circuit breaker boxes, fuse boxes, and electrical panels shall be protected from physical damage and kept in good condition. All fuses and circuits shall be labeled to identify the circuit location.
The storage of any item that obstructs access to any circuit box shall be prohibited.
(c) The permanent use of extension cords in guest rooms shall be prohibited.
Individual branch circuits, including multipl-eplug outlet strips that contain fuse breakers and multiple-plug outlet adapters that do not exceed the amperage for which the outlets are rated, shall be permitted.
Empty light sockets shall be prohibited.
(Authorized by and implementing K.S.A. 2008 Supp. 36-506; effective June 4, 2010.)