No later than 24 months after the effective date of this regulation, each owner or operator of any emission unit subject to the nitrogen oxide emission limits specified in K.A.R. 28-19-713a or K.A.R. 28-19-713b shall meet the following requirements:
(a) Demonstrate compliance with the applicable emissions limit by performing an emissions test in accordance with 40 C.F.R. 60.8, as adopted by reference in K.A.R. 28-19-720, and either of the following:
- (1) Test method 7, 7A, 7C, 7D, or 7E in appendix A-4 to 40 C.F.R. part 60, as adopted by reference in K.A.R. 28-19-720; or
- (2) any other USEPA test method approved by the department;
- (b) ensure continuous compliance with the applicable emissions limit by installing, calibrating, maintaining, and operating a continuous emission monitoring system (CEMS) for nitrogen oxides that meets the requirements of 40 C.F.R. 60.13 and performance specification 2 in appendix B to 40 C.F.R. part 60, as adopted by reference in K.A.R. 28-19-720;
(c) certify the CEMS at least three months before the compliance demonstration required by subsection (a) pursuant to either of the following:
- (1) The quality assurance procedures in appendix F to 40 C.F.R. part 60, as adopted by reference in K.A.R. 28-19-720; or
- (2) an equivalent quality assurance procedure approved by the department; and
- (d) document compliance by continuously monitoring and maintaining records of nitrogen oxide emissions.
(Authorized by K.S.A. 2009 Supp. 65-3005; implementing K.S.A. 65-3010; effective June 25, 2010.)