Ind. Admin. Code tit. 675, r. 28-1-3
Authority: IC 22-13-2-2; IC 22-13-2-13
Affected: IC 10-19-2; IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36- 7
Sec. 3. (a) Standard for Low-, Medium-, and High-Expansion Foam, NFPA 11, 2005 edition, published by National Fire Protection Association (NFPA), 1 Batterymarch Park, Quincy, Massachusetts 02269-9101 is adopted by reference except as revised hereafter.
(b) The following documents referenced in NFPA 11 are not adopted, are not enforceable, and are for information purposes only:
(c) The following documents referenced in NFPA 11 are adopted and are enforceable:
(d) Delete Section 1.2.2, and substitute to read as follows: For alternate materials, methods, and design see the General Administrative Rules (675 IAC 12-6-11).
(e) Delete subsection 1.4 in its entirety without substitution.
(f) Delete subsection 1.5 in its entirety and substitute "See 675 IAC 12-6-11.".
(g) Amend the following definitions in Chapter 3 to read as follows:
APPROVED means acceptance by the authority having jurisdiction by one (1) of the following methods:
(h) Add the following definitions to Chapter 3 as follows:
(i) Delete subsection 4.2.1.5 in its entirety without substitution.
(j) Amend subsection 4.2.1.6 to read as follows: Water supply or premixed solution shall be protected against freezing.
(k) Delete subsection 4.3.2.1 in its entirety and substitute: Storage Facilities. Foam concentrates and equipment shall be stored in an accessible location not exposed to the hazard they protect. If housed, they shall be in a noncombustible structure. Off-premises supplies shall be of the proper type for use in the systems of the given installation. At the time of a fire, these off-premises supplies shall be accumulated in sufficient quantities, before placing the equipment in operation, to ensure uninterrupted foam production at the design rate for the required period of time.
(l) Amend subsection 4.3.2.5.1 to read as follows: The consumption rates shall be based on the percentage concentrate used in the system design (e.g., three percent (3%) or six percent (6%) or other, if so listed).
(m) Delete subsection 4.7.1.3 without substitution.
(n) Insert subsection 4.8.1 Fixed Systems. These systems are complete installations in which foam is piped from a central foam station, discharging through fixed delivery outlets to the hazard to be protected. Any required pumps are permanently installed.
(o) Insert subsection 4.8.2 Semifixed Systems. These systems are the type in which the hazard is equipped with fixed discharge outlets connected to piping that terminates at a safe distance. The fixed piping installation might or might not include a foam maker. Necessary foam- producing materials are transported to the scene after the fire starts and are connected to the piping.
(p) Insert subsection 4.8.3 Mobile Systems. These systems include any foam-producing unit that is mounted on wheels and that is self- propelled or towed by a vehicle. These units can be connected to a suitable water supply or can utilize a premixed foam solution.
(q) Insert subsection 4.8.4 Portable Systems. These systems are the type in which the foam-producing equipment and materials, hose, etc., are transported by hand.
(r) Delete subsection 4.9.2.3 without substitution.
(s) Delete subsection 4.9.2.4 without substitution.
(t) Delete subsection 4.9.2.5.2 without substitution.
(u) Delete subsection 4.9.2.7 in its entirety and substitute: Where automatic shutdown is required, an alarm condition shall remain until manually reset.
(v) Amend Section 5.2.4.3.2 by deleting the "," between "approved" and "for".
(w) Amend Section 5.2.5.1.3 by inserting "securely" before "attached".
(x) Amend Section 5.2.5.1.5 by inserting "a" before "seal".
(y) Amend Section 5.2.6.4 by inserting "as specified in 675 IAC 12-6-11" after "testing laboratories".
(z) Delete Chapter 7 and substitute the following: Plans and specifications shall be filed as required by the General Administrative Rules (675 IAC 12).
(aa) Delete subsection 8.3.4.1 in its entirety without substitution.
(bb) Amend Section 8.3.4.2 by inserting "." at the end of each sentence for items (1), (2), and (3).
(cc) Delete subsection 8.5.1.4 without substitution.
(dd) Amend Section 6.5.2 by deleting "in the opinion of the authority having jurisdiction".
(ee) Delete Section 6.7.1.1.1 in its entirety without substitution.
(ff) Amend Section 6.11.3.3 by deleting "acceptable to" and substituting "approved by".
(gg) Amend Section 9.1.1 by deleting "where required by the AHJ".
(hh) Delete Section 9.12.2 in its entirety without substitution.
(ii) Amend Section 10.3.1 to read as follows: The completed system shall be tested by trained personnel.
(jj) Amend Section 10.3.2 to read as follows: The tests shall be adequate to determine that the system has been properly installed and that it functions as intended.
(kk) Delete in Section 11.1.6, "competent" and substitute "trained".
(ll) Chapter 2 and the appendices are not adopted as part of this code and are intended for use as a guide, and the standards referenced therein are not enforceable as part of this code.
(Fire Prevention and Building Safety Commission; 675 IAC 28-1-3; filed Aug 23, 2006, 4:03 p.m.: 20060906-IR-675050104FRA; readopted filed Aug 8, 2012, 8:08 a.m.: 20120905-IR- 675120260RFA; readopted filed Jul 3, 2018, 2:22 p.m.: 20180801-IR-675180204RFA; readopted filed Jun 10, 2024, 8:09 a.m.: 20240710-IR-675230794RFA)