Ind. Admin. Code tit. 675, r. 15-2-52
Authority: IC 22-13-2-13
Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15
Sec. 52. (a) Minimum Size. The size of water supply piping and branch lines shall not be not less than sizes shown in Table 1B, as follows:
| TABLE 1B | |||
| Minimun [sic.] Size Tubing and Pipe for Water Distribution Systems | |||
| Tubing (Nominal) | Pipe | ||
| Number of Fixtures | Dia. (Inches) | Outer Dia. (Inches) | Iron Pipe Size (Inches) |
| 1 | 1/4* | 3/8 | 1/2 |
| 2 | 3/8 | 1/2 | 1/2 |
| 3 | 1/2 | 5/8 | 1/2 |
| 4 | 1/2 | 5/8 | 1/2 |
| 5 or more | 3/4 | 7/8 | 3/4 |
| *6 feet maximum length. | |||
(b) Sizing Procedure. Both hot and cold water systems shall be computed by the following method:
(Fire Prevention and Building Safety Commission; 675 IAC 15-2-52; filed Mar 25, 1986, 1:44 pm: 9 IR 1997, eff Jun 15, 1986; readopted filed Nov 29, 2001, 12:21 p.m.: 25 IR 1306; readopted filed Sep 21, 2007, 9:20 a.m.: 20071010-IR-675070388RFA; readopted filed Oct 10, 2007, 9:16 a.m: 20071031-IR-675070388RFA; readopted filed Aug 4, 2011, 8:35 a.m.: 20110831-IR-675110254RFA; readopted filed Mar 10, 2017, 9:37 a.m.: 20170405-IR-675170005RFA; readopted filed May 11, 2023, 2:22 p.m.: 20230607-IR-675230104RFA)