Ind. Admin. Code tit. 675, r. 15-2-100
Authority: IC 22-13-2-13
Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15
Sec. 100. (a) The following method shall be employed in computing the supply cord and distribution panelboard load for each feeder assembly for each mobile structure and shall be based on a three (3) wire, one hundred fifteen/two hundred thirty (115/230) volt supply with one hundred fifteen (115) volt loads balanced between the two (2) legs of the three (3) wire system.
Small Appliance Watts: Number of circuits times one thousand five hundred (1500) volt amperes for each twenty (20) ampere appliance receptacle circuit (see definition of "appliance, small" with note); e.g., Number of circuits × 1500 = _____ small appliance volt-amperes.
Total load for determining power supply is the summation of:
(E) Derive amperes for free-standing range (as distinguished from separate ovens and cooking units) by dividing values below by two hundred thirty (230) volts.
| Nameplate Rating | Use | ||
|---|---|---|---|
| 10,000 w × or less | 80% of rating | ||
| 10,001 - 12,500 w | 8,000 v-a | ||
| 12,501 - 13,500 w | 8,400 v-a | ||
| 13,501 - 14,500 w | 8,800 v-a | ||
| 14,501 - 15,500 w | 9,200 v-a | ||
| 15,501 - 16,500 w | 9,600 v-a | ||
| 16,501 - 17,500 w | 10,000 v-a |
A mobile structure is 70 × 10 feet and has two (2) portable appliance circuits, a 1000 watt 230 volt heater, a 200 watt 115 volt exhaust fan, a 400 watt 115 volt dishwasher and a 7000 watt electric range.
| Lighting and small appliance load. | |||||
|---|---|---|---|---|---|
| Lighting 70 × 10 × 3 = | 2100 v-a | ||||
| Small appliance 1500 × 2 = | 3000 v-a | ||||
| Laundry 1500 × 1 = | 1500 v-a | ||||
| 6600 v-a | |||||
| 1st 3000 at 100% | 3000 | ||||
| Remainder (5100 - 3000 = 2000) @ 35% | 1260 | ||||
| 4260 | |||||
| 4260 | = 185 amperes per leg | ||||
| 230 | |||||
| 1000 watt (heater) divided by 230 = | 4.4 amp | ||||
| 200 watt (fan) divided by 115 = | 1.7 amp | ||||
| 400 watt (dishwasher) divided by 115 = | 3.5 amp | ||||
| 7000 watt (range) × .8 divided by 230 = | 24.0 amp | ||||
| Amperes Per Leg | |||||
| A | B | ||||
| Lighting and appliances | 18.5 | 18.5 | |||
| Heater (230 volt) | 4 | 4 | |||
| Fan (115 volt) | 2 | – | |||
| Dishwasher (115 volt) | – | 4 | |||
| Range | 24 | 24 | |||
| Totals | 48.5 | 50.5 | |||
(2) Method No. 2; Optional Method of Calculation for Lighting and Appliance Loads. For mobile structures served by a single three (3) wire one hundred fifteen/two hundred thirty (115/230) volt set of feeder conductors with an ampacity of one hundred (100) or greater, the total load for determining the feeder ampacity may be computed in accordance with Table 100(a)(2) instead of the methods specified in (a)(1). Feeder conductors whose demand load is determined by this optional calculation shall be permitted to have the neutral load determined by section 220-22 of the Indiana Electrical Code ( 675 IAC 17-1 [ 675 IAC 17-1 was repealed filed Feb 17, 1987, 3:15 p.m.: 10 IR 1389, eff Mar 1, 1987 [ IC 4-22-2-36 suspends the effectiveness of a rule document for thirty (30) days after filing with the secretary of state. LSA Document #86-153 was filed Feb 17, 1987.].]). The loads identified in Table 6B, below as "other load" and as "remainder of other load" shall include the following:
(E) The largest of the following: (i) air-conditioning load; (ii) the sixty-five percent (65%) diversified demand of the central electric space heating load; (iii) the sixty-five percent (65%) diviersified [sic.] demand of the load of less than four (4) separately-controlled electric space heating units; (iv) the connected load of four (4) or more separately controlled electric space heating units.
| TABLE 6B | |
| Optional Calculation for Mobile Structures with 100-Amperes or Larger Service | |
| Load (in kW or kVA) | Demand Factor (Percent) |
| Air-conditioning and cooling, including heat pump compressor | 100 |
| Central electric space heating | 65 |
| Less than four (4) separately controlled electric space heating units | 65 |
| First ten (10) kW of all other load | 100 |
| Remainder of other load | 40 |
(Fire Prevention and Building Safety Commission; 675 IAC 15-2-100; filed Mar 25, 1986, 1:44 pm: 9 IR 2022, eff Jun 15, 1986; errata, 9 IR 2931; errata, 9 IR 3093; readopted filed Nov 29, 2001, 12:21 p.m.: 25 IR 1306; readopted filed Sep 21, 2007, 9:20 a.m.: 20071010-IR-675070388RFA; readopted filed Oct 10, 2007, 9:16 a.m: 20071031-IR-675070388RFA; readopted filed Aug 4, 2011, 8:35 a.m.: 20110831-IR-675110254RFA; readopted filed Mar 10, 2017, 9:37 a.m.: 20170405-IR-675170005RFA; readopted filed May 11, 2023, 2:22 p.m.: 20230607-IR-675230104RFA)