Authority: IC 13-15-1-2; IC 13-15-2-1; IC 13-18-3-1; IC 13-18-4-1
Affected: IC 13-11-2; IC 13-13-5-1; IC 13-18-2
Sec. 5. (a) The information required in this section shall be provided:
- (1) when a construction permit application is submitted; or
- (2) in accordance with section 6 of this rule as a postconstruction submittal.
(b) The following information shall be provided for a production well, whether it is proposed for construction or modification:
- (1) The type of proposed well described as tubular, gravel pack, radial collector, rock, or other type of well.
- (2) The type of drilling method described as rotary, cable tool, bucket, or other type of drilling method.
- (3) The depth of the proposed well.
(4) The following information regarding the casing of the proposed well:
- (A) Length.
- (B) Diameter of the casing.
- (C) Diameter of the borehole.
(D) Casing material characteristics, including the following:
- (i) Material type.
- (ii) Schedule or thickness.
- (iii) Pressure rating if polyvinyl chloride (PVC) is utilized as the casing material.
(E) Relative elevation or mean sea level elevation of the following:
- (i) Top of casing.
- (ii) Finished well house floor or slab.
- (iii) Top of gravel pack.
- (iv) Pump base.
- (v) Finished grade.
(5) The following information regarding the well screen:
- (A) Material type.
- (B) Length.
- (C) Diameter.
- (D) Slot size of screen.
- (E) Design entrance velocity.
(F) Elevation of the following:
- (i) Top of screen.
- (ii) Base of screen.
(6) The following information regarding the grout:
- (A) Material type.
- (B) Depth and the extent of the grouting.
(7) The following information regarding the well pump:
- (A) Type.
- (B) Total dynamic head.
- (C) Number of stages.
- (D) Rated capacity.
- (E) Pump curves.
- (F) Type of lubrication.
- (G) Provisions for power source.
- (H) Provisions for emergency operation.
- (8) A description of equipment utilized for water level measurement.
(9) The following information regarding the discharge piping:
- (A) Material type.
- (B) Pressure rating.
- (C) Diameter.
- (D) Description of the flow measuring equipment.
(E) Location of the following:
- (i) Check valve.
- (ii) Shut off valve.
- (iii) Pressure gauge.
- (iv) Smooth nosed sample tap.
- (v) Air relief or vacuum relief valves where applicable.
- (vi) Threaded or flanged port for maintenance and testing.
(c) The plans required to be submitted with an application for construction permit under 327 IAC 8-3-3 must include a cross section and plan view of the applicable proposed production well mechanics that includes the following:
- (1) Overall depth.
- (2) Depth of grouting.
- (3) Well screen location.
- (4) Casing details.
- (5) Discharge piping or raw water transmission main and components.
- (6) Well house and other protective equipment.
- (7) Pumping equipment.
- (8) Storage equipment.
- (9) Water treatment equipment.
(Water Pollution Control Division; 327 IAC 8-3.4-5; filed Jun 17, 1999, 1:50 p.m.: 22 IR 3369; readopted filed Jan 10, 2001, 3:23 p.m.: 24 IR 1518; readopted filed Nov 21, 2007, 1:16 p.m.: 20071219-IR-327070553BFA; readopted filed Jul 29, 2013, 9:21 a.m.: 20130828-IR-327130176BFA; readopted filed Jun 14, 2019, 1:59 p.m.: 20190710-IR-327190246BFA; readopted filed Oct 18, 2024, 1:57 p.m.: 20241113-IR-327230810RFA)