Ind. Admin. Code tit. 327, r. 8-3.4-14
Authority: IC 13-14-8; IC 13-15-1-2; IC 13-15-2-1; IC 13-18-3-1; IC 13-18-4-1
Affected: IC 13-11-2; IC 13-13-5-1; IC 13-18-2; IC 22-12
Sec. 14. (a) A hydropneumatic storage tank shall conform with the following:
(4) Provide housing as follows:
(5) Be equipped to provide the following:
(C) Control equipment consisting of the following:
(iii) Air addition as follows:
(b) The usable capacity of a hydropneumatic storage tank must meet one (1) of the following:
(c) Unless required by IC 22-12 or 680 IAC to be certified by ASME, a hydropneumatic storage tank shall be certified by American National Standards Institute (ANSI), The American Society of Mechanical Engineers (ASME), National Sanitation Foundation (NSF International), or Underwriter's Laboratories, Inc. (UL). The applicant must submit information showing that the tank used is properly certified.
(d) Hydropneumatic tank storage of water shall not be designated for fire protection purposes.
(e) A hydropneumatic tank shall not be used in a community public water system when more than four hundred (400) persons are served.
(f) If more than one (1) hydropneumatic tank is used in series, each tank must:
(Water Pollution Control Division; 327 IAC 8-3.4-14; filed Jun 17, 1999, 1:50 p.m.: 22 IR 3373; readopted filed Jan 10, 2001, 3:23 p.m.: 24 IR 1518; filed Apr 24, 2006, 3:00 p.m.: 29 IR 2966; readopted filed Nov 21, 2007, 1:16 p.m.: 20071219-IR-327070553BFA; readopted filed Jul 29, 2013, 9:21 a.m.: 20130828-IR-327130176BFA; readopted filed Jun 14, 2019, 1:59 p.m.: 20190710-IR-327190246BFA; readopted filed Oct 18, 2024, 1:57 p.m.: 20241113-IR-327230810RFA)