Authority: IC 13-14-8; IC 13-18-12-4
Affected: IC 13-18-12
Sec. 6. (a) A storage or treatment facility must be maintained and operated to prevent any threats to human health or the environment as follows:
- (1) An all-weather off-loading area with containment for spill cleanup must be provided where the vehicle contents are received by the storage or treatment facility.
- (2) Unauthorized access to the storage or treatment facility must be prevented by locks, and the storage or treatment facility must be fenced and posted.
- (3) The storage or treatment facility must be maintained so there is no discharge or seepage of septage other than controlled removal for final disposal of the septage.
- (4) The storage or treatment facility must be maintained to prevent safety hazards or disease vector conditions.
(b) Any uncovered storage structure must allow for and maintain a minimum of two (2) feet of freeboard at all times.
(c) Stockpiles of solids resulting from septage treatment at the treatment facility must be:
- (1) stored on an impervious surface;
- (2) stored for not longer than thirty (30) days at any given time;
- (3) maintained to have adequate run-on and run-off control methods; and
- (4) covered by a tarp, plastic sheet, or roof if stored for longer than seventy-two (72) hours.
(Water Pollution Control Division; 327 IAC 7.1-5.1-6; filed Mar 3, 2022, 10:40 a.m.: 20220330-IR- 327140029FRA; readopted filed Oct 18, 2024, 1:57 p.m.: 20241113-IR-327230810RFA)