Sec. 22. (a) Ventilation shall be provided for all pump stations.
(b) No interconnection of ventilation systems shall exist between wet wells and dry wells.
(c) All intermittently operated ventilation equipment shall be electrically interconnected with the respective lift station lighting systems.
(d) All manual ventilation and lighting switches shall override any automatic controls.
(e) All fan wheels shall be fabricated from nonsparking material.
(f) Dry wells that are located underground shall be provided with mechanical ventilation in accordance with the following:
(g) Wet wells with screens or mechanical equipment shall be equipped with permanently installed mechanical ventilation in accordance with the following:
(h) All pulleys and belts shall be of a static electricity dissipating type.
(Water Pollution Control Division; 327 IAC 3-6-22; filed May 17, 1999, 12:11 p.m.: 22 IR 3096; readopted filed Apr 11, 2005, 2:45 p.m.: 28 IR 2470; readopted filed Jun 15, 2011, 11:15 a.m.: 20110713-IR-327110193BFA; readopted filed Jun 29, 2017, 9:34 a.m.: 20170726-IR-327170225BFA; readopted filed May 12, 2023, 1:07 p.m.: 20230607-IR-327230079BFA; readopted filed Oct 18, 2024, 1:57 p.m.: 20241113-IR- 327230810RFA)