Ind. Admin. Code tit. 326, r. 2-9-14
Authority: IC 13-14-8; IC 13-15-2; IC 13-17-3-4; IC 13-17-3-11
Sec. 14. (a) Any stationary internal combustion source, including any combination of turbines, reciprocating engines, or engines, may elect to comply with this section by complying with section 1 of this rule and limiting fuel usage for every twelve (12) month period to less than the limits found in:
(b) Sources electing to comply with subsection (a)(1) must be able to demonstrate compliance not later than thirty (30) days after receipt of a written request by the department or U.S. EPA. No other demonstration of compliance shall be required. A source specific operating agreement is not required for these sources.
(c) Sources electing to comply with subsection (a)(2) must:
(d) For sources complying with subsection (a)(2), the following records shall be kept at the source:
(e) Table 1 limits shall be as follows:
| TABLE 1 | |
| Fuel | Maximum Fuel Usage per Year |
| Large turbine | |
| Natural gas | 227.27 MMCF/yr |
| Distillate | 1,414.42 kgal/yr |
| Uncontrolled natural gas prime movers | |
| Gas turbines | 294.11 MMCF/yr |
| 2-cycle lean burn | 37.03 MMCF/yr |
| 4-cycle lean burn | 31.25 MMCF/yr |
| 4-cycle rich burn | 43.47 MMCF/yr |
| Diesel, reciprocating | |
| <600 HP | 165.51 kgal/yr |
| Gasoline, reciprocating | |
| <250 HP | 12.26 kgal/yr |
| Diesel, large stationary | 235.45 kgal/yr |
| Unit abbreviations: | |
| kgal = 103 gallons | |
| MMCF = 106 cubic feet | |
(f) Table 2 limits shall be as follows:
| TABLE 2 | |
| Fuel | Maximum Fuel Usage per Year |
| Large turbine | |
| Natural gas | 363.63 MMCF/yr |
| Distillate | 2,263.07 kgal/yr |
| Uncontrolled natural gas prime movers | |
| Gas turbines | 470.58 MMCF/yr |
| 2-cycle lean burn | 59.25 MMCF/yr |
| 4-cycle lean burn | 50.00 MMCF/yr |
| 4-cycle rich burn | 69.56 MMCF/yr |
| Diesel, reciprocating | |
| <600 HP | 264.82 kgal/yr |
| Gasoline, reciprocating | |
| <250 HP | 19.62 kgal/yr |
| Diesel, large stationary | 376.72 kgal/yr |
| Unit abbreviations: | |
| kgal = 103 gallons | |
| MMCF = 106 cubic feet | |
(Air Pollution Control Division; 326 IAC 2-9-14; filed May 7, 1997, 4:00 p.m.: 20 IR 2315; readopted filed Oct 22, 2004, 10:35 a.m.: 28 IR 814; filed Sep 28, 2011, 10:56 a.m.: 20111026-IR-326070286FRA; filed Feb 6, 2012, 2:54 p.m.: 20120307-IR- 326090493FRA; readopted filed Oct 18, 2024, 2:09 p.m.: 20241113-IR-326230809RFA)