Ind. Admin. Code tit. 312, r. 13-9-1
Authority: IC 25-39-4-2; IC 25-39-4-9
Affected: IC 25-39
Sec. 1. (a) Except as provided in subsection (d), the following procedures shall be used for the disinfection of drilled wells:
(1) The amount of water in the well shall be determined by multiplying the gallons per foot by the number of feet of water in the well according to the following table:
| Diameter of Well in Inches | Gallons Per Foot |
|---|---|
| 2 | .16 |
| 3 | .37 |
| 4 | .65 |
| 5 | 1.00 |
| 6 | 1.50 |
| 8 | 2.60 |
| 10 | 4.10 |
| 12 | 6.00 |
(2) At least one hundred (100) parts per million of chlorine concentration in water are required for disinfection. For each one hundred (100) gallons of water in the well, the amount of chlorine liquid or compound shown in the following table shall be used:
| Laundry Bleach | Hypochlorite Granules |
|---|---|
| (5.25% chlorine) | (70% chlorine) |
| 3 cups | 2 ounces |
(b) As used in this section, one (1) cup is equivalent to an eight (8) ounce measuring cup.
(c) As used in this section, one (1) ounce is equivalent to one (1) heaping tablespoon of granules.
(d) This section does not apply to a monitoring well or a dewatering well.
(Natural Resources Commission; 312 IAC 13-9-1; filed Nov 22, 1999, 3:34 p.m.: 23 IR 772; readopted filed Aug 4, 2005, 6:00 p.m.: 28 IR 3661; readopted filed May 20, 2011, 3:28 p.m.: 20110615-IR-312110002RFA; readopted filed Jul 19, 2017, 3:45 p.m.: 20170816-IR-312170132RFA; readopted filed May 17, 2023, 10:52 a.m.: 20230614-IR-312230069RFA)