425 ILCS 60/3
(d) It shall be the responsibility of the owner of a structure to supply and install all required detectors. The owner shall be responsible for making reasonable efforts to test and maintain detectors in common stairwells and hallways. It shall be the responsibility of a tenant to test and to provide general maintenance for the detectors within the tenant's dwelling unit or rooming unit, and to notify the owner or the authorized agent of the owner in writing of any deficiencies which the tenant cannot correct. The owner shall be responsible for providing one tenant per dwelling unit with written information regarding detector testing and maintenance.
The tenant shall be responsible for replacement of any required batteries in the smoke detectors in the tenant's dwelling unit, except that the owner shall ensure that such batteries are in operating condition at the time the tenant takes possession of the dwelling unit. The tenant shall provide the owner or the authorized agent of the owner with access to the dwelling unit to correct any deficiencies in the smoke detector which have been reported in writing to the owner or the authorized agent of the owner.
(e) The requirements of this Section shall apply to any dwelling unit in existence on July 1, 1988, beginning on that date. Except as provided in subsections (f) and (g), the smoke detectors required in such dwelling units may be either: battery powered provided the battery is a self-contained, non-removable, long-term battery, or wired into the structure's AC power line, and need not be interconnected.
(1) The battery requirements of this Section shall apply to battery-powered smoke detectors that:
(2) The battery requirements of this Section do not apply to:
(B) a fire alarm, smoke detector, smoke alarm, or ancillary component that uses:
(f) In the case of any dwelling unit that is newly constructed, reconstructed, or substantially remodelled after December 31, 1987, the requirements of this Section shall apply beginning on the first day of occupancy of the dwelling unit after such construction, reconstruction or substantial remodelling. The smoke detectors required in such dwelling unit shall be permanently wired into the structure's AC power line, and if more than one detector is required to be installed within the dwelling unit, the detectors shall be wired so that the actuation of one detector will actuate all the detectors in the dwelling unit.
In the case of any dwelling unit that is newly constructed, reconstructed, or substantially remodeled on or after January 1, 2011, smoke detectors permanently wired into the structure's AC power line must also maintain an alternative back-up power source, which may be either a battery or batteries or an emergency generator.
(g) Every hotel shall be equipped with operational portable smoke-detecting alarm devices for the deaf and hearing impaired of audible and visual design, available for units of occupancy.
Specialized smoke detectors for the deaf and hearing impaired shall be available upon request by guests in such hotels at a rate of at least one such smoke detector per 75 occupancy units or portions thereof, not to exceed 5 such smoke detectors per hotel. Incorporation or connection into an existing interior alarm system, so as to be capable of being activated by the system, may be utilized in lieu of the portable alarms.
Operators of any hotel shall post conspicuously at the main desk a permanent notice, in letters at least 3 inches in height, stating that smoke detector alarm devices for the deaf and hearing impaired are available. The proprietor may require a refundable deposit for a portable smoke detector not to exceed the cost of the detector.
(from Ch. 127 1/2, par. 803)
(Source: P.A. 100-200, eff. 1-1-23; 102-46, eff. 1-1-22; 102-558, eff. 8-20-21.)