Ill. Admin. Code tit. 83, § 600.310
b) The test shall be conducted in accordance with the standards for testing Cold Water Meters as prescribed by the American Water Works Association (AWWA C705-60) with quantities and flows for positive displacement meters as follows:
| TEST FLOWS (G.P.M.) & QUANTITY | |||||||||
| MINIMUM | INTERMEDIATE | MAXIMUM | |||||||
| Size of | Flow | QUANTITY | FLOW | QUANTITY | FLOW | QUANTITY | |||
| meter | G.P.M. | Gal. | Cu.Ft. | G.P.M. | Gal. | Cu.Ft. | G.P.M. | Gal. | Cu.Ft. |
| ⅝" | ¼ | 10 | 1 | 2 | 10 | 1 | 15 | 100 | 10 |
| ¾" | ½ | 10 | 1 | 3 | 10 | 1 | 25 | 100 | 10 |
| 1" | ¾ | 10 | 1 | 4 | 10 | 1 | 40 | 100 | 10 |
| 1½" | 1½ | 100 | 10 | 8 | 100 | 10 | 80 | 1000 | 100 |
| 2" | 2 | 100 | 10 | 15 | 100 | 10 | 120 | 1000 | 100 |
| 3" | 4 | 100 | 10 | 20 | 100 | 10 | 250 | 1000 | 100 |
| 4" | 7 | 100 | 10 | 40 | 100 | 10 | 350 | 1000 | 100 |
| 6" | 12 | 100 | 10 | 60 | 100 | 10 | 700 | 1000 | 100 |
No meters shall be placed in service when the accuracy is different than follows:
| NEW METERS | REPAIRED METERS | |
| MINIMUM RANGE | 95-101.5% | 90-101.5% |
| INTERMEDIATE RANGE | 98.5-101.5% | 98.5-101.5% |
| MAXIMUM RANGE | 98.5-101.5% | 98.5-101.5% |