- a) These drawings with specifications shall show the complete heating, steam piping, ventilation and air conditioning systems; plumbing, drainage and stand pipe systems; laundry and kitchen ventilation.
b) Heating, steam piping, air conditioning and ventilation including:
- 1) Radiators and steam heated equipment, such as sterilizers, warmers, and steam tables.
- 2) Heating and steam mains and branches with pipe sizes.
- 3) Diagram of heating and steam risers with pipe sizes.
- 4) Sizes, types and heating surfaces of boilers; furnace with stokers and oil burners, if any.
- 5) Pumps, tanks, boiler breeching, piping and boiler room accessories.
- 6) Air conditioning systems with required equipment, water and refrigerant piping and ducts.
- 7) Supply and exhaust ventilating systems with necessary duct work and piping.
- 8) Air quantities for all room supply and exhaust ventilating duct openings.
c) Plumbing, drainage, and stand pipe systems including:
- 1) Size and elevation of street sewer, house sewer, house drains, street water main, and water service into the building.
- 2) Location and size of soil, waste, and vent stacks with connections to house drains, clean outs, fixtures, and equipment.
- 3) Size and location of hot, cold, and circulating mains, branches, and risers from the service entrance and tanks.
- 4) Riser diagram to show all plumbing stacks with vents, water risers, and fixture connections.
- 5) Gas, oxygen, and special connections.
- 6) Stand pipe and sprinkler systems.
- 7) Plumbing fixtures and fixtures which require water and drain connections.
Mechanical drawings shall include:
(Source: Amended at 13 Ill. Reg. 6562, effective April 17, 1989)