- a) Duplex grounding type receptacles shall be installed in all areas or rooms in sufficient quantities for the tasks to be performed.
- b) The duplex receptacles for general procedures and minor procedures such as laser or endoscopy must be hospital grade.
- c) A minimum of two duplex receptables shall be located convenient to each examination and work table, and to each Stage I recovery space.
- d) A minimum of one duplex receptacle for each wall shall be installed in each work area or room, other than storage or locker room.
- e) Duplex receptables for cleaning equipment and general use shall be installed in all corridors.