a) Radiographic Suite: if radiographic studies are conducted, the following shall apply:
- 1) Radiographic rooms shall have a minimum clear area of 120 square feet and a minimum clear dimension of 10', exclusive of vestibule, toilet, closet, cabinet, and work counter (whether fixed or movable). A minimum of 3'0" clearance shall be at each side and both ends of the radiographic table;
- 2) A handwashing sink with a plaster trap within the room;
- 3) A communication system connected to the control station;
- 4) A film processing area with work counters, triple sink, storage cabinets, exhaust venting for chemicals, open drains, and safety lighting, if required by the facility operational narrative;
- 5) A viewing and administration area;
- 6) Film storage facilities, if required by the facility operations narrative;
- 7) A toilet room with handwashing facilities, directly accessible from each radiographic room without entering the general corridor area; and
- 8) A dressing area with convenient access to toilets and a lockable closet unit for patient's belongings.
b) If laboratory testing is performed in the facility, the laboratory area of the facility shall contain the following minimum facilities:
- 1) A laboratory work counter with sink and vacuum, and electric services.
- 2) A lavatory or counter sink equipped for handwashing.
- 3) A storage cabinet or closet for any necessary laboratory supplies and equipment. This storage area may be combined with other storage areas in the center.
- 4) Blood collection facilities with space for a chair and work counter.
(Source: Amended at 48 Ill. Reg. 13763, effective August 28, 2024)