Ill. Admin. Code tit. 62, § 220.80
a) High-voltage circuits; protective devices.
1) Circuit breakers protecting high-voltage circuits supplying power to portable or mobile equipment must:
i) short circuit,
b) Monthly testing, examination, and maintenance of circuit breakers; procedures; high-voltage.
2) Tests must include:
3) The operator must maintain written records of each test, examination, repair, or adjustment of all circuit breakers protecting high-voltage circuits. Such records must be kept in a book containing the following information:
Circuit breakers and auxiliary devices located on the surface protecting surface or underground circuits, or both, must be examined and tested at least once (1) each month by a person qualified to perform testing and calibration, or qualified to perform electrical work under Section 220.50(e).
c) Annual testing, examination, and maintenance of circuit breakers; procedures; high-voltage.
1) The annual test and examination must include:
A) In resistance grounded systems:
B) In ungrounded and solidly grounded systems:
5) The operator must maintain written records of each test, examination, repair, or adjustment of all circuit breakers protecting high-voltage circuits. Such records must be kept in a book containing the following information:
Circuit breakers and auxiliary devices located on the surface protecting surface or underground circuits, or both, must be tested and calibrated at the time of installation and at least annually thereafter by a person qualified to perform testing and calibration or qualified to perform electrical work under Section 220.50(e).
d) Grounding resistors.
The grounding resistor, where required must be of the proper ohmic value to limit the voltage drop in the grounding circuit external to the resistor to not more than one hundred (100) volts under ground fault conditions. The grounding resistor shall be rated for maximum fault current continuously and insulated from ground for a voltage equal to the phase-to-phase voltage of the system.
e) Grounding resistors; continuous current rating.
The ground fault current rating of grounding resistors must meet the "extended time rating" set forth in Institute of Electrical and Electronics Engineers, Inc., 345 E. Forty-Seventh Street, New York City, New York 10017, Standard No. 32 (1972, reaffirmed in 1984) (The reference does not include any later amendments or editions.)
f) Protection of high-voltage circuits; neutral grounding resistors.
5) Grounding transformers, where used to derive a neutral, must:
g) High-voltage cables; minimum design requirements.
h) Cable couplers and connection boxes; minimum design requirements.
1) Cable couplers; requirements.
2) Connection Boxes
i) Connection of single-phase loads.
Single-phase loads must be connected phase-to-phase in resistance grounded systems.
j) Installation of high-voltage transmission cables.
High-voltage transmission cables must be installed or placed so as to afford protection against damage. They must be placed to prevent contact with low-voltage or communication circuits.
k) High-voltage power lines; clearances above ground.
High-voltage power lines located above driveways, haulageways, and railroad tracks must be installed so as to provide the minimum vertical clearance as specified in Rule 232 of the National Electrical Safety Code published by the Institute of Electrical and Electronics Engineers, Inc., 345 E. 47th Street, New York, New York 10017 (1981). (The reference does not include any later amendments or editions.); provided, however, that in no event shall any high-voltage power line be installed less than fifteen (15) feet above ground, walkways, or working areas.
l) Booms and masts; minimum distance from high-voltage lines.
The booms and masts of equipment operated on the surface of any coal mine must not be operated within ten (10) feet of an energized overhead powerline. Where the voltage of overhead powerlines is sixty-nine thousand (69,000) volts, or more, the minimum distance from the boom or mast must be as follows:
| Nominal Powerline Voltage (In 1,000 volts) | Minimum Distance Feet | |
| 69-114 | 12 | |
| 115-229 | 15 | |
| 230-499 | 25 | |
| 500 or more | 35 |
m) Movement of equipment: minimum distance from high-voltage lines.
When any part of any equipment operated on the surface of any coal mine is required to pass under or by any energized high-voltage power line and the clearance between such equipment and powerline is less than that specified in subsection (l) for booms and masts, such power lines must be deenergized or other precautions must be taken.
n) Operating of rear dump trucks under powerlines.
In cases where dump trucks are operated under powerlines, the minimum vertical clearance that must be maintained over dumping areas, must be five (5) feet more than the maximum height of the truck bed measured with the truck bed in the extreme raised position.
o) Disconnecting devices.
Disconnecting devices must be installed at the beginning of each branch line in high-voltage circuits, except disconnecting devices in high-voltage transmission lines, which must be accessible and located as near as practicable to the entrance to the high-voltage stationary installations supplied from the overhead powerlines, and must be equipped or designed in such manner that it can be determined by visual observation that the circuit is deenergized when such devices are open.
p) Identification of circuit breakers and disconnecting switches.
Circuit breakers and disconnecting switches must be labeled to show which units they control, unless identification can be made readily by location.
q) High-voltage equipment grounding.
Low resistance ground fields used in high-voltage systems serving portable or mobile equipment must be separated from the other ground fields by twenty-five (25) feet or more.
r) Movement of portable substation and transformers.
Portable substations, transformers, and high-voltage switch gear must be deenergized before they are moved from one location to another, and must be examined by a qualified person under Section 220.50(e) to assure safe operating condition prior to reenergization.
s) Performing work in proximity to energized high-voltage circuits.
Work must not be performed within four (4) feet of any exposed energized high-voltage conductor unless the provisions of subsections (v) through (dd) have been complied with, with respect to guarding of all energized conductors; except that, a person qualified under Section 220.50(e) and wearing protective lineman's gloves rated for the phase-to-phase voltage of the system, may disconnect and connect conductors to the load side of opened fused cutouts or disconnecting switches.
t) Work on high-voltage line; deenergizing and grounding.
High-voltage lines must be deenergized and grounded before work is performed on them, except that repairs may be permitted on energized high-voltage line if:
u) Work on high-voltage line.
1) A high-voltage line is not regarded as deenergized for the purpose of performing work on it, until it has been determined by a qualified person under subsection (ff) that such high-voltage line has been deenergized and grounded. Such qualified person must by visual observation:
2) Work must not be performed on any high-voltage line which is supported by any pole or structure which also supports other high-voltage lines until:
v) Repairs to energized high-voltage lines.
1) The operator has determined that:
2) The operator has designated a qualified person under subsection (ff) as the person responsible for carrying out such repairs and such person, in order to insure protection for himself and other qualified persons assigned to perform such repairs from the hazards of such repairs, has prepared and filed with the operator:
An energized high-voltage line may be repaired only when:
w) Work on energized high-voltage surface line; reporting.
Any operator designating and assigning qualified persons to perform repairs on energized high-voltage surface lines under the provisions of subsection (v) must maintain a record of such repairs. Such record must contain a notation of the time, date, location, and general nature of the repairs made, together with a copy of the information filed with the operator by the qualified person designated as responsible for performing such repairs.
x) Simultaneous repairs.
When two (2) or more persons are working on an energized high-voltage surface line simultaneously, and any one of them is within reach of another, such person must not be allowed to work on different phases or on equipment with different potentials.
y) Installation of protective equipment.
1) Before repair work on energized high-voltage surface lines is begun, protective equipment must be used to cover all bare conductors, ground wires, guys, telephone lines, and other attachments in proximity to the area of planned repairs. Such protective equipment must be installed from a safe position below the conductors or other apparatus being covered. Each rubber protective device employed in making repairs must have a dielectric strength of twenty thousand (20,000) volts or more and must comply with the provisions of the American Society for Testing and Materials (ASTM) 655 Fifteenth Street N.W.; Washington, D.C. 20005 as follows:
| ITEM | ASTM STANDARD | DATE OF ADOPTION |
| Rubber Insulating gloves | D120-87 | July 31, 1987 |
| Rubber matting for use around electrical apparatus | D178-88 | Nov. 29, 1987 Feb. 26, 1988 |
| Rubber insulating blankets | D1048-88 | Feb. 26, 1988 |
| Rubber insulating hoods | D1049-83 | June 24, 1983 |
| Rubber insulating line hose | D1050-85 | August 30, 1985 |
| Rubber insulating sleeves | D1051-87 | July 31, 1987 |
AGENCY NOTE: The standards do not include any later amendments or editions.
3) Only live line tool poles having a manufacturer's certification to withstand the following minimum tests shall be used:
z) Protective clothing; use and inspection.
2) All rubber protective equipment used for work on energized high-voltage surface lines must be electrically tested in accordance with the American National Standards Institute and the American Society for Testing and Materials Standards (ASTM), 655 Fifteenth Street N.W.; Washington, D.C. 20005 as follows:
| ITEM | ASTM STANDARD | DATE OF ADOPTION |
| Rubber Insulating gloves | D120-87 | July 31, 1987 |
| Rubber insulating blankets | D1048-88 | Feb. 26, 1988 |
| Rubber insulating hoods | D1049-83 | June 24, 1983 |
| Rubber insulating line hose | D1050-85 | August 30, 1985 |
| Rubber insulating sleeves | D1051-87 | July 31, 1987 |
AGENCY NOTE: The references do not include any later editions or references.
aa) Protective equipment; inspection.
Each person must visually inspect protective equipment and clothing provided him in connection with work on high-voltage surface lines before using such equipment and clothing and any equipment or clothing containing any defect or damage must be discarded and replaced with proper protective equipment or clothing prior to the performance of any electrical work on such lines.
bb) Protective equipment; testing and storage.
1) All rubber protective equipment used on work on energized high-voltage surface lines must be electrically tested by the operator in accordance with subsection (z)(2) and such testing must be conducted in accordance with the following schedule:
cc) Operating disconnecting or cutout switches.
Disconnecting or cutout switches on energized high-voltage surface lines must be operated only with insulated sticks, fuse tongs, or pullers which are adequately insulated and maintained to protect the operator from the voltage to which he is exposed. When such switches are operated from the ground, the person using such devices must wear protective rubber lineman's gloves except where switches are bonded to a metal mat as provided in subsection (t).
dd) Tying into energized high-voltage surface circuits.
If the work of forming an additional circuit by tying into an energized high-voltage surface line is performed from the ground any person performing such work must wear and employ all the protective equipment and clothing required and tested under the provisions of subsections (z), (aa), and(bb). In addition, the insulated stick used by such person must have been designed for such purpose and must be adequately insulated and be maintained to protect such person from the voltage to which he is exposed.
ee) Use of grounded messenger wires; ungrounded systems.
Solely for purposes of grounding ungrounded high-voltage power systems, grounded messenger wires used to suspend the cable of such systems may be used as a grounding medium.
ff) Repair of energized surface high-voltage line; qualified person.
An individual is a qualified person for the purpose of repairing energized surface high-voltage lines, under subsections (t) through (ee) only if such person:
(Source: Amended at 13 Ill. Reg. 5955, effective April 18, 1989)