Ill. Admin. Code tit. 62, § 220.180
a) Cutout switches.
Trolley wires and trolley feeder wires, shall be provided with cutout switches at intervals of not more than two thousand (2,000) feet and near the beginning of all branch lines.
b) Overcurrent protection.
Trolley wires and trolley feeder wires shall be provided with overcurrent protection.
c) Devices for overcurrent protection.
Automatic circuit interrupting devices that will deenergize the affected circuit upon occurrence of a short circuit at any point in the system will meet the requirements of Section 220.180(b).
d) Insulation of trolley wires, wires; guarding of trolley wires and trolley feeder wires, and bare signal trolley feeder wires.
1) Trolley wires, trolley feeder wires, and bare signal wires shall be adequately guarded: