a) At a minimum, continuous monitors for the following parameters shall be installed on air pollution control equipment subject to this Subpart:
- 1) Destruction device combustion temperature;
- 2) Temperature rise across a catalytic afterburner bed;
- 3) Breakthrough of volatile organic material on a carbon adsorption unit;
- 4) Outlet gas temperature of a refrigerated condenser;
- 5) Temperature of a non-refrigerated condenser coolant supply system.
- b) Each monitor shall be equipped with a recording device.
- c) Each monitor shall be calibrated quarterly.
- d) Each monitor shall operate at all times while the associated control equipment is operating.
(Source: Amended at 15 Ill. Reg. 8018, effective May 14, 1991)