- a) all appurtenances, specific structures, or equipment having any connection with the planned water treatment improvements;
- b) detailed hydraulic profiles of water flowing through treatment systems;
- c) schematic plumbing for all structures and equipment;
d) location of feeders, piping layout, and points of application;
- e) locations of the sources of pollution listed in 35 Ill. Adm. Code 604.150(a);
- f) for sites subject to flooding, the maximum flood level based upon the highest flood level specified in the best available information, such as the flood of record, the 100-year flood projection, or the 500-year flood projection;
g) security provisions; and
h) stability and corrosion control:
- 1) existing and proposed finished water quality, including:
A) Hardness;
- B) Calcium;
- C) Alkalinity;
- D) pH;
- E) Orthophosphate;
- F) Silicate;
- G) Total Dissolved Solids;
- H) Oxidation-reduction potential (ORP);
- I) Temperature;
J) Chloride;
- K) Sulfate;
- L) Iron;
- M) Manganese;
- N) Chlorine residual (total);
- O) Chlorine residual (free); and
- 2) a recommendation of the treatment necessary to reduce corrosion in household plumbing.
The following information must be submitted on plans for the construction of treatment facilities:
(Source: Amended at 47 Ill. Reg. 7449, effective May 16, 2023)