Ill. Admin. Code tit. 35, § 229.APPENDIX B
An "X" in any box in this matrix means that measurement of that parameter is required.
| MINIMUM FREQUENCY | CONTROL SYSTEM | ||||||
| Operating Parameters | Data Measurement | Data Recording | Dry Scrubber Followed by Fabric Filter | Wet Scrubber | Dry Scrubber Followed by Fabric Filter and Wet Scrubber | Selective Noncatalytic Reduction System | |
| Maximum Charge Rate1 | Continuous | Once per hour | X | X | X | X | |
| Maximum Fabric Filter Inlet Temperature | Continuous | Once per minute | X | X | |||
| Maximum Flue Gas Temperature | Continuous | Once per minute | X | X | |||
| Minimum Secondary Chamber Temperature | Continuous | Once per minute | X | X | X | X | |
| Minimum Dioxin/Furan Sorbent Flow Rate | Hourly | Once per hour | X | X | |||
| Minimum HCl Sorbent Flow Rate | Hourly | Once per hour | X | X | |||
| Minimum Reagent Flow Rate | Hourly | Once per hour | X | ||||
| Minimum Hg Sorbent Flow Rate | Hourly | Once per hour | X | X | |||
| Minimum Pressure Drop Across the Wet Scrubber or Minimum Horsepower or Amperage to Wet Scrubber | Continuous | Once per minute | X | X | |||
| Minimum Scrubber Liquor Flow Rate | Continuous | Once per hour | X | X | |||
| Minimum Scrubber Liquor pH | Continuous | Once per hour | X | X | |||
1For batch HMIWIs, record the charge per batch.
(Source: Amended at 35 Ill. Reg. 16615, effective September 30, 2011)