- a) In addition to the reporting requirements in other Parts of Agency regulations, the licensee shall report the following events if not reported under other Parts of Agency regulations:
- 1) Source stuck in an unshielded position.
- 2) Any fire or explosion in a radiation room.
- 3) Damage to the source racks.
- 4) Failure of cable or drive mechanism used to move the source racks.
- 5) Inoperability of the access control system.
6) Detection of radiation source by the product exit monitor.
- 7) Detection of radioactive contamination attributable to licensed radioactive material.
- 8) Structural damage to the pool liner or walls.
- 9) Abnormal water loss or leakage from the source storage pool.
10) Pool water conductivity exceeding 100 microsiemens per centimeter.
- b) The report shall include a telephone report within 24 hours as described in 32 Ill. Adm. Code 340.1220 and a written report within 30 days as described in 32 Ill. Adm. Code 340.1230.
(Source: Amended at 47 Ill. Reg. 9201, effective June 22, 2023)