Fla. Admin. Code R. 69A-21.304
(2) Whenever a pre-engineered system is installed, inspected, repaired, maintained or otherwise serviced, the permittee shall complete an inspection report containing, at a minimum, the information in paragraphs (a) through (o), in this subsection. One copy shall be signed by and delivered to the owner, or the representative of the owner of the facility in which the system was installed. The other copy shall be retained in the fire equipment dealer’s files for a period of not less than three years after the last inspection.
(k) A drawing of a new installation; a first inspection; or whenever changes are made. The drawing shall include the following as a minimum:
1. Sizes of the hood, plenum, and ducts.
2. Sizes, types and locations of cooking appliances.
3. Positions of all nozzles, identification of nozzles, their distances from the hazards that they protect.
4. Positions of all detectors.
5. Diagram of the entire piping installation.
(l) Responses to the following questions:
1. Were the inspection and maintenance performed in accordance with the presently adopted editions of NFPA (indicate standard(s) used? (“No” answers require an explanation).
2. Was the system tagged in accordance with rule 69A-21.303, F.A.C.? (“No” answers require an explanation).
3. Were the inspection and maintenance performed in accordance with the manufacturer’s manual and the manufacturer’s specifications? (“No” answers require an explanation).
Rulemaking Authority 633.104 FS. Law Implemented 633.104, 633.308, 633.216 FS. History–New 2-7-89, Amended 10-20-93, 11-21-01, Formerly 4A-21.304.