Fla. Admin. Code R. 62-814.460
(1) Computations to establish compliance with the standards set forth in rule 62-814.450, F.A.C., shall be performed by the use of the Bonneville Power Administration (BPA) Corona and Field Effects Program for calculating electric and magnetic fields set forth in paragraphs 62-814.470(1) and (2), F.A.C., below. When electric and magnetic field calculations are made using the BPA Corona and Field Effects Program, the following input data will be used:
(a) Magnetic field calculations.
1. The MCR currents will be used.
2. The conductor will be at its minimum clearance to the earth.
3. Currents will be assumed to be balanced in phase and in magnitude with no zero-sequence current.
(b) Electric field calculations.
1. The highest operating voltage will be used.
2. The conductor will be at its minimum clearance to the earth or other conductor height, whichever produces the highest electric field along the ROW.
3. Voltages will be assumed to be balanced in phase and in magnitude.
Rulemaking Authority 403.061(7), 403.523(1) FS. Law Implemented 403.061(31), 403.523(14) FS. History–New 3-21-89, Amended 1-7-93, Formerly 17-274.460, 17-814.460.