D.C. Mun. Regs. tit. 22-A, § 3833
3833.1 Each MHCRF shall comply with all applicable provisions of the D.C. Fire Code and the Fire Safety Provisions of the D.C. Property Maintenance Code (Chapter 7).
3833.2 Each MHCRF shall obtain an annual inspection of the facility by FEMSD, which shall determine the facility's compliance or non-compliance with fire safety requirements; provided that fire safety inspections for new construction or substantial renovation of a structure may be performed by DCRA in accordance with DCRA and FEMSD procedures and the requirements of the Construction Codes.
3833.3 Each MHCRF shall have a written Emergency Preparedness Plan with instructions that is approved by FEMSD. The plan shall be followed in case of fire, explosion, or any other emergency and shall be available for review in each MHCRF.
3833.4 The plan shall be updated annually, as necessary, and include the following:
(6) Fire alarm annunciators and controls; and
(7) Portable fire extinguishers;
3833.10 No MHCRF shall permit smoking in bedrooms.3833.11 A fire extinguisher with a minimum rating of 210 (BC) that is effective in extinguishing grease and oil fires shall be located within fifteen feet (15 ft.) of any stove, oven, cooking burner, or other cooking device.3833.12 Each MHCRF shall have at least one (1) working fire extinguisher with a minimum rating of 210 (BC) on each floor, including the basement and first floor, in a central location accessible to residents and employees.3833.13 A fire extinguisher with a minimum rating of 210 (BC) of a type and capacity sufficient to extinguish fires originating in the main heating plant and hot water heater shall be located within five feet (5 ft.) of this equipment.3833.14 Each fire extinguisher shall be:- (a) Properly maintained;
- (b) Approved for its specific use by an official of the FEMSD; and
- (c) Inspected by FEMSD annually and in accordance with the International Fire and Construction Codes cited in § 3833.1.3833.15 Each fire extinguisher shall be recharged immediately after use and properly tagged.3833.16 Each fire extinguisher shall have attached to it a tag giving the date when the service was performed, a description of the service performed, and the name and address of the person performing the service.3833.17 Each MHCRF shall have a fire exit that is:- (a) Clearly designated on the MHCRF's emergency preparedness plan;
- (b) Clearly identified for residents;
- (c) Kept clear of obstructions; and
- (d) Accessible from sleeping rooms.3833.18 If the area or floor served by a fire exit door is to be occupied, the door shall not require a key to unlock the door from the inside and shall not require more than thirty (30) seconds to unlock.
3833.19 Each MHCRF that has residents in sleeping rooms above the second floor, or that has more than eight (8) residents in sleeping rooms above the street level, shall:
(a) Provide access to two (2) separate means of exit for sleeping rooms above street level, at least one (1) of which shall consist of an enclosed interior stair, a horizontal exit, or a fire escape, all arranged to provide a safe path of travel to the outside of the building without traversing any corridor or space exposed to an unprotected vertical opening; or
(b) Otherwise comply with D.C. Fire Code.
SOURCE: Final Rulemaking published at 65 DCR 1633 (February 16, 2018).