D.C. Mun. Regs. tit. 20, § 3530
3530.1 The BEPS in this section apply to all privately-owned buildings with at least 50,000 square feet of gross floor area, and all District-owned or District instrumentality-owned buildings with at least 10,000 square feet of gross floor area, that are not subject to BEPS in Subsection 3530.2 or 3530.3. The “ENERGY STAR Score” column lists the BEPS for property types that can receive an ENERGY STAR® Score. The “Source EUI” column lists the BEPS for buildings that cannot receive an ENERGY STAR Score. All Energy Use Intensity (EUI) values are kBtu/ft2 unless otherwise noted.
| Property Type | 2021 Building Energy Performance Standard | |
|---|---|---|
| ENERGY STAR Score | Source EUI | |
| Adult Education | 110.4 | |
| Ambulatory Surgical Center | 426.9 | |
| Aquarium | 240.2 | |
| Automobile Dealership | 124.1 | |
| Bank Branch | 71 | 153.7 |
| Bar/Nightclub | 297 | |
| Barracks | 56 | 141.4 |
| Bowling Alley | 206.6 | |
| Casino | 240.2 | |
| College/University | 180.6 | |
| Convenience Store with Gas Station | 592.6 | |
| Convenience Store without Gas Station | 592.6 | |
| Convention Center | 192 | |
| Courthouse | 71 | 153.7 |
| Data Center | 50 | 1.8 Total Energy kBtu/IT Energy kBtu |
| Distribution Center | 19 | 103.7 |
| Drinking Water Treatment & Distribution | 5.9 kBtu/gallons per day | |
| Enclosed Mall | 170.7 | |
| Energy/Power Station | 229.4 | |
| Fast Food Restaurant | 886.4 | |
| Financial Office | 71 | 153.7 |
| Fire Station | 185.5 | |
| Fitness Center/Health Club/Gym | 206.6 | |
| Food Sales | 592.6 |
| Food Service | 527.7 | |
|---|---|---|
| Hospital (General Medical & Surgical) | 50 | 426.9 |
| Hotel | 54 | 183.9 |
| Ice/Curling Rink | 206.6 | |
| Indoor Arena | 240.2 | |
| K-12 School | 36 | 139 |
| Laboratory | 318.2 | |
| Library | 206.4 | |
| Lifestyle Center | 228.8 | |
| Mailing Center/Post Office | 242.6 | |
| Medical Office | 62 | 172 |
| Mixed Use Property | 229.4 | |
| Movie Theater | 240.2 | |
| Multifamily Housing | 66 | 110.7 |
| Museum | 240.2 | |
| Non-Refrigerated Warehouse | 19 | 103.7 |
| Office | 71 | 153.7 |
| Other | 229.4 | |
| Other – Education | 110.4 | |
| Other - Entertainment/Public Assembly | 240.2 | |
| Other - Lodging/Residential | 143.6 | |
| Other – Mall | 225.3 | |
| Other - Public Services | 229.4 | |
| Other – Recreation | 206.6 | |
| Other - Restaurant/Bar | 573.7 | |
| Other – Services | 242.6 | |
| Other - Specialty Hospital | 426.9 | |
| Other – Stadium | 240.2 | |
| Other - Technology/Science | 229.4 | |
| Other – Utility | 229.4 | |
| Outpatient Rehabilitation/Physical Therapy | 426.9 | |
| Performing Arts | 240.2 | |
| Personal Services (Health/Beauty, Dry Cleaning, etc.) | 242.6 | |
| Police Station | 185.5 | |
| Pre-school/Daycare | 131.5 | |
| Prison/Incarceration | 156.4 | |
| Race Track | 240.2 | |
| Refrigerated Warehouse | 19 | 235.6 |
| Repair Services (Vehicle, Shoe, Locksmith, etc.) | 242.6 | |
| Residence Hall/Dormitory | 56 | 141.4 |
| Residential Care Facility | 213.2 | |
|---|---|---|
| Restaurant | 573.7 | |
| Retail Store | 64 | 401.2 |
| Roller Rink | 206.6 | |
| Self-Storage Facility | 21.2 | |
| Senior Care Community | 50 | 213.2 |
| Social/Meeting Hall | 192 | |
| Stadium (Closed) | 240.2 | |
| Stadium (Open) | 240.2 | |
| Strip Mall2 | 228.8 | |
| Supermarket/Grocery Store | 64 | 401.2 |
| Swimming Pool | 206.6 | |
| Transportation Terminal/Station | 240.2 | |
| Urgent Care/Clinic/Other Outpatient | 426.9 | |
| Veterinary Office | 145.8 | |
| Vocational School | 110.4 | |
| Wastewater Treatment Plant | 50 | 7.5 kBtu/gallons per day |
| Wholesale Club/Supercenter | 64 | 401.2 |
| Worship Facility | 17 | 140.3 |
| Zoo | 240.2 |
3530.2 The BEPS in this section apply to Hospital Campuses. The “ENERGY STAR Score” column lists the BEPS for property types that can receive an ENERGY STAR Score. The “Source EUI” column lists the BEPS for buildings that cannot receive an ENERGY STAR Score. All Energy Use Intensity (EUI) values are kBtu/ft2.
| Property Type | 2021 Building Energy Performance Standard | |
|---|---|---|
| ENERGY STAR Score | Source EUI | |
| Ambulatory Surgical Center | 138.3 | |
| Hospital (General Medical & Surgical) | 50 | 433.9 |
| Other - Specialty Hospital | 433.9 | |
| Outpatient Rehabilitation/Physical Therapy | 138.3 | |
| Urgent Care/Clinic/Other Outpatient | 145.8 |
3530.3 The BEPS in this section apply to College/University Campuses. Because College/University Campuses cannot receive an ENERGY STAR Score like other property types, DOEE is using a Blended Custom Source Energy Use Intensity Metric instead. The “Source EUI” column lists the BEPS for each campus. All
metrics for campuses are Blended Custom Source Energy Use Intensity (EUI) measured in kBtu/ft2.
| Campus | Source EUI |
|---|---|
| American University Main Campus | 207.1 |
| American University Law Campus | 180.6 |
| Catholic University Main Campus | 248.6 |
| Gallaudet University Main Campus | 199.3 |
| Georgetown University Main Campus | 262.0 |
| Georgetown University Law Campus | 190.4 |
| George Washington University Main Campus | 241.4 |
| George Washington University Mt. Vernon Campus | 209.9 |
| Howard University Main Campus | 235.8 |
| Howard University West Campus | 202.0 |
| Trinity University Main Campus | 202.6 |
| University of District of Columbia | 180.6 |
3530.4 The 2021 BEPS shall remain in effect until DOEE establishes new BEPS.
3530.5 A building does not meet the BEPS if, based on the 2019 District Benchmark Results and Compliance Report for that building:
3530.6 An owner of a building that does not meet the BEPS and whose building experienced atypical business activity, such that the 2019 District Benchmark Results and Compliance Report does not represent normal operations of the
building, may request the use of their Calendar Year 2018 District Benchmark Results and Compliance Report by submitting a 2021 BEPS variance request form to DOEE for review and approval through the Online BEPS Portal no later than January 1, 2022.
3530.7 An owner of a building that does not meet the BEPS may request that DOEE establish a variance for their building by submitting a 2021 BEPS variance request form to DOEE for review and approval through the Online BEPS Portal no later than August 1, 2021. The request must include evidence that the building meets one of the following special circumstances:
(a) No single property use type makes up more than fifty-percent (50%) of the overall building gross floor area, so the owner should therefore receive a variance that accounts for the percentage of each property type within the building; or
(b) For a building belonging to a property type where fewer than ten (10) buildings are used to determine the BEPS for that property type, there is an alternative industry-recognized peer group data set with an equivalent metric for the building's property type.
SOURCE: Final Rulemaking published at 68 DCR 4643 (April 30, 2021).