- (a) Except for a dispenser, no owner or operator of an UST system shall move a component of an UST system for use at another location, including another location at the same underground storage facility, without the prior written approval of the commissioner. Any approval under this section may include any conditions the commissioner deems appropriate. For purposes of section 22a-449(d)-111 of the UST regulations, the life expectancy of a tank or piping that routinely contains product relocated under this section shall be based on the date such tank or piping was originally installed, not the date such tank or piping was relocated.
- (b) An owner or operator of an UST system shall not install or reinstall a dispenser from another location, including from another location at the same underground storage facility, unless such dispenser is equipped with a containment sump that meets the requirements of an under-dispenser containment sump.
(Effective July 28, 1994; Amended May 7, 2025)