Conn. Agencies Regs. § 22a-174-30a
(a) Definitions. For the purposes of this section, the definitions provided in this subsection shall apply. Terms used in this section that are not defined in this subsection are as defined in section 22a-174-1 of the Regulations of Connecticut State Agencies.
(b) Applicability.
(c) Requirements.
(1) No owner or operator of a GDF shall transfer or allow the transfer of gasoline between a delivery vehicle and a GDF stationary storage tank unless such stationary storage tank is equipped with a Stage I vapor recovery system that includes:
(3) The pressure specifications for any pressure/vacuum vent valve shall be as follows:
(i) A positive pressure setting of:
(i) A positive pressure setting of 2.5 to 6.0 inches of water,(ii) A negative pressure setting of 6.0 to 10.0 inches of water, and(iii) The total leak rate of all pressure/vacuum vent valves at an affected facility, including connections, shall not exceed 0.17 cubic foot per hour at a pressure of 2.0 inches of water and 0.63 cubic foot per hour at a vacuum of 4 inches of water.
(6) In addition to the requirements of subdivisions (1) to (5), inclusive, of this subsection, an owner or operator of any GDF that has a monthly throughput of 100,000 gallons or more shall install, operate and maintain a Stage I vapor recovery system that meets the requirements of subparagraphs (A) to (F), inclusive, of this subdivision. If a GDF ever exceeds a monthly throughput of 100,000 gallons, the requirements of this subdivision shall thereafter apply.
(d) Testing.
(1) The owner or operator of any GDF shall conduct each of the following tests at least once per calendar year:
(9) Any owner or operator of any GDF shall:
(e) Record keeping.
(1) Any owner or operator of a GDF shall maintain the following records:
(Effective July 8, 2015)