- (a) A fused disconnecting means or a circuit breaker device of the lowest current rating consistent with the load requirements of the ***power supply shall be provided for power service to the ***power supply. This device may be included within the ***power supply housing or it may be in a separate weatherproof enclosure. such enclosure shall be acceptable to the power company.
- (b) Where the power service protective device is in an enclosure which is external to and not part of the ***power supply case, this enclosure and the ***power supply case shall be made electrically continuous by a means other than the power service neutral conductor.
- (c) Properly identified line and neutral terminals for connecting electrical service conductors shall be provided. All power service connections at the CATV ***power supply shall be such as to preclude the possibility of a reversal in polarity.
- (d) CATV power supply equipment shall be designed so as to provide a separate, permanent electrical interconnection between the service neutral conductor terminal, metallic enclosure ***and the CATV cable strand.
(Effective November 25, 1969)