49 C.F.R. § 192.125
(b) Copper pipe used in service lines must have wall thickness not less than that indicated in the following table:
| Standard size inch (millimeter) | Nominal O.D. inch (millimeter) | Wall thickness inch (millimeter) | |
|---|---|---|---|
| Nominal | Tolerance | ||
| 1⁄2 (13) | .625 (16) | .040 (1.06) | .0035 (.0889) |
| 5⁄8 (16) | .750 (19) | .042 (1.07) | .0035 (.0889) |
| 3⁄4 (19) | .875 (22) | .045 (1.14) | .004 (.102) |
| 1 (25) | 1.125 (29) | .050 (1.27) | .004 (.102) |
| 11⁄4 (32) | 1.375 (35) | .055 (1.40) | .0045 (.1143) |
| 11⁄2 (38) | 1.625 (41) | .060 (1.52) | .0045 (.1143) |
[35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192-62, 54 FR 5628, Feb. 6, 1989; Amdt. 192-85, 63 FR 37502, July 13, 1998]