Cooking systems using liquefied petroleum gas (LPG) and compressed natural gas (CNG) must meet the following requirements:
- (a) The design, installation and testing of each LPG system must meet ABYC A-1, “Marine Liquefied Petroleum Gas (LPG) Systems,” Chapter 6 of NFPA 302, or other standard specified by the Commandant.
- (b) The design, installation and testing of each CNG system must meet ABYC A-22, “Marine Compressed Natural Gas (CNG) Systems,” Chapter 6 of NFPA 302, or other standard specified by the Commandant.
(c) Cooking systems using Chapter 6 of NFPA 302 as the standard must meet the following additional requirements:
- (1) The storage or use of CNG containers within the accommodation area, machinery spaces, bilges, or other enclosed spaces is prohibited;
- (2) LPG or CNG must be odorized in accordance with ABYC A-1 appendix 4 or A-22 appendix 4, respectively;
- (3) The marking and mounting of LPG cylinders must be in accordance with ABYC A-1 appendix 7; and
- (4) LPG cylinders must be of the vapor withdrawal type as specified in ABYC A-1 section 1.7.
- (d) Continuous pilot lights or automatic glow plugs are prohibited for an LGP or CNG installation using ABYC A-1 or A-22 as the standard.
(e) CNG installation using ABYC A-22 as the standard must meet the following additional requirements:
- (1) The storage or use of CNG containers within the accommodation area, machinery spaces, bilges, or other enclosed spaces is prohibited;
- (2) CNG cylinders, regulating equipment, and safety equipment must meet the installation, stowage, and testing requirements of paragraph 6-5.12 of NFPA 302.
- (3) The use or stowage of stoves with attached CNG cylinders is prohibited as specified in paragraph 6-5.1 of NFPA 302.
- (f) If the fuel supply line of an LPG or CNG system enters an enclosed space on the vessel, a remote shutoff valve must be installed that can be operated from a position adjacent to the appliance. The valve must be located between the fuel tank and the point where the fuel supply line enters the enclosed portion of the vessel. A power operated valve installed to meet this requirement must be of a type that will fail closed.
(g) The following variances from ABYC A-1 section 1.12 are allowed for CNG:
- (1) The storage locker or housing access opening need not be in the top.
- (2) The locker or housing need not be above the waterline.
(h) The following variances from NFPA 302 are allowed:
- (1) The storage locker or housing for CNG tank installations need not be above the waterline as required by paragraph 6-5.12.1.1(a);
- (2) Ignition protection need not be provided as required by paragraph 6-5.4.
Note to § 184.240: The ABYC and NFPA standards referenced in this section require the posting of placards containing safety precautions for gas cooking systems.
[CGD 85-080, 61 FR 1002, Jan. 10, 1996, as amended by USCG-2000-7790, 65 FR 58465, Sept. 29, 2000]