(c) Each cable entering a box or fitting must be protected from abrasion, and must meet the following requirements:
(g) Except as provided in paragraph (i) of this section, each armored cable must have a metallic covering that is—
(2) Grounded at each end of the run to—
(l) Each conductor, except a fixture wire within a box, must have a free space computed using the volume per conductor given in Table 169.680(l). If a fitting or device such as a cable clamp, hickey, switch or receptacle is contained in the box, each fitting or device must count as one conductor.
| Size of conductor A.W.G. | Free space for each conductor in box, cubic inches |
|---|---|
| 14 | 2.0 |
| 12 | 2.25 |
| 8 | 2.50 |
| 1 | 3.0 |