The following information must be displayed on a permanent metal or pressure-sensitive nameplate attached to each agent storage cylinder/valve assembly:
- (a) Manufacturer's name, address, and telephone number;
- (b) Coast Guard approval number assigned to the system under 46 CFR 159.005-13;
- (c) Identifying mark of the laboratory;
- (d) Reference to the laboratory's listing standard;
- (e) Type of extinguishing agent;
- (f) Operating pressure at 70 °Fahrenheit;
- (g) Storage temperature range;
- (h) Factory test pressure of the cylinder;
- (i) Reference to the manufacturer's marine design, installation, operation, and maintenance manual;
- (j) Weight of agent charge and gross weight of cylinder/valve assembly;
- (k) Minimum maintenance instructions; and
- (l) Any other information required by the laboratory or another government agency.