46 C.F.R. § 132.220
(a) Each portable fire extinguisher approved under subpart 162.028 of this chapter and each semi-portable fire extinguisher approved under subpart 162.039 of this chapter must be installed in compliance with Table 132.220 of this section. The placement of each extinguisher must satisfy the cognizant OCMI, who may also deem added extinguishers necessary for the proper protection of the vessel.
| Space | Minimum required rating | Number and placement |
|---|---|---|
| Safety areas: Communicating passageways | 2-A | 1 in each main passageway, not more than 45.7 m (150 ft) apart (permissible in stairways). |
| Pilothouse | 20-B:C | 2 in the vicinity of the exit. |
| Service spaces: Galleys | 40-B:C | 1 for each 230 sq m (2,500 sq ft) or fraction thereof, suitable for hazards involved. |
| Paint lockers | 40-B | 1 outside space, in the vicinity of the exit. |
| Accessible baggage and storerooms | 2-A | 1 for each 230 sq m (2,500 sq ft) or fraction thereof, located in the vicinity of the exits, either inside or outside spaces. |
| Workshops and similar spaces | 2-A | 1 outside space in the vicinity of the exit. |
| Machinery spaces: Internal-combustion propulsion-machinery | 40-B:C | 1 for each 1,000 brake horsepower, but not fewer than 2 and more than 6. |
| 120-B | 1 required. 1 2 | |
| Electric propulsion motors or generators of open type | 40-B:C | 1 for each propulsion motor or generator unit. |
| Auxiliary spaces: Internal combustion | 40-B | 1 outside space in the vicinity of the exit.2 |
| Electric motors and emergency generators | 40-B:C | 1 outside space in the vicinity of the exit.2 |
| Spares | 2-A | 10 percent of the required number rounded up. |
| 40-B:C | 10 percent of the required number rounded up. | |
| 1 Not required where a fixed gaseous fire extinguishing system is installed. | ||
| 2 Not required on vessels of less than 300 GT. |
[CGD 82-004 and CGD 86-074, 62 FR 49348, Sept. 19, 1997, as amended by USCG-2012-0196, 81 FR 48271, July 22, 2016]