- (a) Each fuse in a general emergency alarm system must meet the requirements of part 111, subpart 111.53, of this chapter.
- (b) Each overcurrent protection device must cause as wide a differential as possible between the rating of the branch circuit overcurrent protection device and that of the feeder overcurrent protection device.
- (c) The capacity of the feeder overcurrent device must be as near practicable to 200 percent of the load supplied. The capacity of a branch circuit overcurrent device must not be higher than 50 percent of the capacity of the feeder overcurrent device.
[CGD 94-108, 61 FR 28289, June 4, 1996]